Charging
Cycle Applications: Limit initial current
to 3600mA. Charge until battery voltage (under charge) reaches 14.40 to
14.70 volts at 68º F (20º C). Hold at 14.40 to 14.70 volts until current
drops to approximately 180mA. Battery is fully charged under these
conditions, and charger should either be disconnected or switched to
"float" voltage.
"Float" or "Stand-by Service": Hold battery
across constant voltage source of 13.50 to 13.80 volts continuously. When
held at this voltage, the battery will seek its own current level and
maintain itself in a fully charged condition. |